| WinNUTVersion | Win 95 | Win 95 OSR2 | Win 98 | Win 98 2nd edition | Win ME | Win NT 4 workstation | Win NT 4 Server | Win 2000 Professional | Win XP | Win 2003 Server |
Windows Vista |
| 2.0.0b |
untested | untested | untested | untested | untested | untested | untested | untested | Tested Good |
Tested Good | Tested Good |
| 2.0.0a | untesed | untested | untested | Tested Good | untested | Tested good (sp6a) | untested | Tested Good | Tested Good | Tested good |
untested |
| 1.2.1a | Tested Good | untested | untested | Tested Good | untested | untested | Tested Good | Tested Good | Tested Good | untested | untested |
| 0.45.2c | untested | untested | untested | Tested Good | untested | untested | untested | Tested Good | Tested Good | untested | untested |
| 0.45.2b | untested(2) | untested(2) | untested(2) | Tested Good(2) | untested(2) | untested(2) | untested(2) | Tested Good(2) | Tested Good(2) | untested | untested |
| 0.45.2a | untested | untested(2) | untested | Tested Good | untested | untested | Tested Good(2) | Tested Good | untested | untested | untested |
| 0.44.1c | untested | untested(2) | untested | Tested Good | untested | untested | untested | Tested Good | untested | untested | untested |
| 0.44.1b | untested | Tested Good(2) | untested | Tested Good(1) | Tested Good(1) | untested | untested | Tested Good | untested | untested | untested |
| 0.44.1a | Tested Good | Tested Good(2) | untested | Tested Good | Tested Bad(3) | untested | Tested Good | Tested Good | Tested Bad(4) | untested | untested |
| Tested Good means that it successfully shutdown the computer when the ups went critical - caveats to this are the number exceptions below | |
| Tested Bad means it failed to shutdown the computer properly - an explaination is in the numbered list below | |
| Foot notes | |
| 1 | Some programs like Active Desktop don't work well with the forced shutdown in the windows 9x series. In particular ActiveDesktop comes up in safe mode after a forced shutdown. You should just be able to click on the restore button to fix it. |
| 2 | This is now a confirmed bug in all versions up to and including 0.45.2b. IP addresses in the upsmon.conf cannot be resolved properly to connect to the machine running upsd. Workaround is to use a DNS resolvable name (can just add the upsd machines name and ip to the c:\windows\hosts or c:\winnt\system32\drivers\etc\hosts file on the windows machine to make it DNS resolvable) and use that name in the upsmon.conf. The next release will have this fixed |
| 3 | Using the combination of shutdown and poweroff flags in the exit windows API call cause ME to suspend instead of shutdown |
| 4 | Whistler Beta1 blue screened when the UPS went critical - maybe an issue with the beta |
)
so I can update the list. Thanks!